Dent PowerScout 3037

How to connect a Dent PS3037 Meter to Attune

Written by Matt Weissert
Updated over 2 weeks ago

You can use an Attune (fka Senseware) Modbus Bridge, BACnet Bridge, or Pulse Bridge to connect to the Dent PowerScout 3037.

Modbus Bridge

  1. Connect the +- RS-485 terminals to the +- Modbus Sensor Bridge terminals with 2-wire.

  2. Configure the registers you want to read from the Modbus Configuration page in the Attune platform. Reference the Dent PS3037 Meter Manual to see the available registers.

  3. Create and add tiles or charts to a Dashboard to display the data you are collecting from the meter.

Pulse Bridge

A pulse connection provides a simple set-up, but does not provide information available via Modbus, such as line voltage, power factor, etc.

  1. Connect the 2 wires from one of the connectors of the Pulse Sensor Bridge to the Dent digital output connector. Make sure the bridge is configured as 'Bridge Voltage Source' on the Module Configuration page. Connect the Attune bridge to a Node and power the Node. It will automatically start collecting the pulse and send it to the Attune Cloud.

  2. Find your pulse conversion to kWh. This information can be found in the Dent PS3037 Meter Manual and can be configured on the meter.

  3. Create a pulse-based meter in the Meters App.

  4. Add tiles or charts to a Dashboard to display the data you are collecting from the meter.