Attune's Indoor Air Quality (IAQ) and Indoor Environmental Quality (IEQ) Sensor Packages makes it easy to deploy and monitor a variety of environmental conditions in seconds. These packages can provide the following sensor data depending on your ordered configuration:
IAQ Sensors
Temperature, Relative Humidity
Total Volatile Organic Compounds (TVOC)
Particulate Matter (PM1.0, PM2.5, and PM10)
CO₂
Add-on gases: CO (Carbon Monoxide), H₂S (Hydrogen Sulfide), SO₂ (Sulfur Dioxide), O₃ (Ozone), NO₂ (Nitrogen Dioxide), HCHO (Formaldehyde), CH₄ (Methane), Cl₂ (Chlorine), ETO (Ethylene Oxide), HCN (Hydrogen Cyanide), NH₃ (Ammonia), O₂ (Oxygen)
IEQ Sensors
Sound
Light
Motion
Vibration
Pressure
Installation:
Plug the Sensor Package into a wall outlet using the provided wall power adapter (4-5 feet above the ground). Mount the IAQ to the wall using the Attune Mounting Backplate.
Note: Be sure to mount the IAQ vertically, not horizontally, in order to ensure proper airflow for accurate temperature/relative humidity readings when other sensors are present.
Standard Sensors Calibration:
The sensors are all factory calibrated. Once installed, the CO₂ and VOC sensors automatically adjust and will reach full operational accuracy within 24-48 hours, although readings will be available before this time (Read more about ABC algorithm here). The Temperature, Humidity, and PM Sensors do not need to be recalibrated once installed. All the sensors have very low drift and their expected life time is 10 years.
Special Gas Sensors Calibration:
Bridge Version 3.7.6
Ozone and NO2 can be manually offset to 0 using the hard reset bridge button. Make sure the environment is free of those contaminants before performing this operation.
Bridge Version 3.7.0 and above
Attune switched to a new sensor manufacturer for special add-on gases. The sensors are factory calibrated and they have a life expectancy of 3-10 years, depending on the type of gas.
Bridge Version 3.4.5
CO, H₂S, SO₂, O₃, and NO₂ sensors can be manually calibrated to 'zero' when in clean air by performing a hard reset. For other versions of the sensor, please contact Attune in regards to manually zeroing or spanning the sensor.
Bridge Version 3.4.6.
The IAQ bridge will automatically offset using baseline values for CO, H₂S, SO₂, O₃, and NO₂ sensors. Once powered, the minimum values will be measured over increasing periods of time in order to automatically offset the sensor data using the calculated baseline levels. This process will become more accurate the longer the sensor is powered; the process will begin anew if the package gets unpowered. This functionality is not suitable in environments will persistently elevated levels of the measured gas; please contact Attune if this will be the case to discuss other calibration options.
Technical Specifications:
Power:
IAQ/IAQ Plus/IEQ: 5VDC from Node via micro-USB connector
IAQ Lite (T/RH/CO2): 6xAA Lithium Batteries, ~2 yr at 5min Poll
Standard IAQ Sensors
Temperature (°F/°C) / Relative Humidity (%): T/RH: ± 0.3°C, RH: ± 2%
Carbon Dioxide (CO₂): 400-5000 ppm +/- 25 ppm, ± 3% of reading
Volatile Organic Compounds (TVOC): 0-60000 ppb
Particulate Matter: PM1.0 (μg/m3) / PM2.5 (μg/m3) / PM4.0 (μg/m3) / PM10 (μg/m3) / # particles ⌀<x μm in 1cm3 of Air (x = 0.5, 1.0, 2.5, 4.0, 10): PM2.5: 0-1000 μg/m3, ± 10%
Particulate Matter (IAQ Plus): PM1.0, PM2.5, PM10 (μg/m3 and pcs/L)
0.3-10μm diameter. 0-1000 μg/m3, ± 3%
Add-on IAQ Sensors
Carbon Monoxide (CO): 0-10/100/1000ppm, ± 5%
Methane (CH4): 0-5%, Range 0-1%Vol: ±0.06%. Range > 1%vol: ±6%
Formaldehyde (HCHO): 0-1000ppb, ± 20ppb or ± 20% m.v.
Hydrogen Sulfide (H₂S): 0-2/100ppm, ± 5%
Nitrogen Dioxide (NO₂): 0-5/50/100ppm, ± 5%
Ozone (O₃): 0-5 ppm, , ± 5%
Sulfur Dioxide (SO₂): 0-5/50/100ppm, ± 5%
IEQ Sensors
Light: Lights On/Off based on lux threshold
Motion: Up to 5m or 12m Detection Distance
Pressure: 0-1psi; ± 0.25%
Sound: 30dBa-130dBa, ± 1.5dBa; 31.5Hz to 8.5KHz
Vibration: Roll/Yaw Range: ± 180°; Pitch Range: ± 90°; Accelerometer Range: ± 2g; Gyroscope Range: ± 2000°/s
Size (inches): 4.3 x 4.3 x 1.7
Weight (ounces): 6*
*Dependent on which sensors are included in the IAQ package